Operating varity

Auto Mode.
Cooling Mode.
Heating Mode.
Fan Mode.
Dry Mode

Dry Mode

 

If the DRY mode is selected from the OFF position, or if the user switched to dry mode from FAN or HEAT modes, the unit will operate with the COOL mode continuously for a period of 12 minutes or till the room temperature gets 1 ºC below the set temperature.
Once this condition has been fulfilled, the dry mode will operate under either A,B, C, or D zones as indicated below:

 

Zone (A): If the room temperature is 2 ºC above setting temperature.
Zone (B): If the room temperature is within 1 ºC above setting temperature.
Comp. ON for 8 mins + OFF for 4 mins + Fan works for 30 Sec .before compressor ON and work with compressor then fan OFF for 30 Sec. after compressor OFF.
Zone (C): If the room temperature is between 1 ºC to 2 ºC below setting temperature.Comp. ON for 6 mins + OFF for 6 mins + Fan works for 30 Sec. before compressor ON and work with compressor then fan OFF for 30 Sec. after compressor OFF.
Zone (D): If the room temperature is 3 ºC below setting temperature.

Other temperature ranges are dead bands or zone stability.

 

            

 

 

 

 

 

 

 

 

 

 

 

 

                       

 

 