Hot Starting Function

HOT START ( Heat Pump Only)
When starting "HEAT" mode, the indoor fan will delay on operation according to indoor coil temperature to asure hot start. During"HEAT" mode, indoor fan will operat as follows:
1- If indoor unit coil temperature is => 30 ºC the fan will run at low speed for 20 seconds.
2- After 20 seconds, the indoor unit fan will resume its user set speed.

 

Anti- Freeze Protection

ANTI-FREEZ protection
This protection is available only in cooling mode to protect the indoor coil from icing when its temperature < = 0 ºC due to low amount of air flow across the coil.
This could be cause by clogging of indoor unit filters or excessive dirt on the cooling coil.
The anti-freeze protection is activated when the indoor coil temperature becomes <= - 2 ºC for 1 minute whilst the compressor is running for at least 10 minutes
The microprocessor will stop both the compressor and the outdoor unit fan.
After a delay time of 3 minutes, the microprossesor will re-operate both the compressor and outdoor unit fan when the indoor coil temperature becomes => 12 ºC for at least 1 minute.

 

 

            

 

 

 

 

 

 

 

 

 

 

 

 

                       

 

 