Defrost Function


The defrost control activated only in the "HEAT" mode to de-ice the outdoor coil.
The defrost controller is of the time and temperature type as indicated in the process below.
- If the temperature increases above 3 ºC for more than 2 minutes, the defrost controller is deactivated and the time is reset.
- When the temperature decreases below 3 ºC, the defrost controller is activated and the
timer starts counting the time period to use it with the outdoor coil temperature in determining when to start the process as follows :
• Should the outdoor coil sensor temperature be <= - 8 ºC for a time period of 30 minutes.
• Should the outdoor coil sensor temperature be <= - 4 ºC for a time period of 1 hour.
• Should the outdoor coil sensor temperature be <= - 2 ºC for a time period of 2 hours.

After either one of the three above cases, the operating mode will change to "COOL" and the microprocessor of the PC-board will stop both the indoor and the outdoor fans.
The defrost Cycle is complete when the outdoor coil temperature sensor reads 10 ºC or after de-icing period of 10 minutes whichever is first.
When the defrost cycle is completed, the operating mode will re-change to "HEAT".

 

 

            

 

 

 

 

 

 

 

 

 

 

 

 

                       

 

 